Economizer HVAC: Types, Operation and Key Requirements
Energy accounts for a significant portion of commercial operating budgets, whether companies are manufacturing pharmaceutical products or accommodating guests in an 82,000-square-foot banquet facility. Any cost-saving towards the heating, ventilation, and air conditioning (HVAC) bill is welcomed. HVAC economizers play a role in this effort as they utilize cold New Jersey air for free cooling.
Tri-Tech Energy’s commercial HVAC services include economizer installation and maintenance. We serve manufacturing, industrial, hospitality, retail, educational, and municipal clients. In this article, we explain what is an economizer in commercial HVAC, how it works, and the different types. We also highlight a couple of prescriptive requirements.
What is an Economizer in HVAC?
An economizer is a mechanical device integrated into a building’s HVAC system to provide ‘free cooling.’ It forms part of the cooling system and uses cooler outdoor air to cool the building’s interior, thereby reducing the need to run the air conditioner’s compressor. Economizers are also used to ventilate buildings.
There are several recommendations and guidelines for effectively deploying an economizer for HVAC, including American National Standards Institute (ANSI)/American Society of Heating, Refrigerating and Air-Conditioning Engineers (ASHRAE)/Illuminating Engineering Society (IES) Standard 90.1-2022–Energy Standard for Sites and Buildings Except Low-Rise Residential Buildings.
How Does an Economizer Work?
There are several types of HVAC economizers, but we will use an air-side economizer to explain how they work. The device consists of the following parts:
- Two outdoor air dampers directly linked to the return air dampers used to control airflow.
- An outdoor air sensor that determines if the outdoor air is acceptable for free cooling.
- An indoor air sensor that reads sensible temperature and maintains discharge or mixed air temperature.
- A control board that receives sensor input signals and calculates the next step before relaying the output signals to the damper actuator and power exhaust motor (if present).
- A damper actuator that moves into the assigned position communicated by the control board to maintain the discharge air or mixed air set point.
When the control board receives sensor inputs that indicate outdoor air is suitable for free cooling, the outdoor air dampers will modulate from their minimum position to maintain the mixed air or discharge air setpoint calculated by the control board, until the appropriate space temperature is achieved.
If the outdoor air is unsuitable, the economizer control board signal relays back to the HVAC system’s control board, which initiates mechanical cooling.
Types of Economizers
There are two main types of HVAC economizers utilized in commercial environments: airside and waterside.
Airside
Airside economizers use dampers to bring cool outside air into the building. Three different control strategies are available based on the system’s sensors.
- Dry-bulb. The sensor only measures the outside air temperature.
- Single enthalpy (wet bulb). Sensors measure the outside air temperature and humidity.
- Differential enthalpy. Two sensors compare the outdoor and return air enthalpy to find the most energy-efficient air mixture.
Waterside
Often used in large commercial systems, waterside economizers use outside air to cool a building’s chilled water system.
Other types of economizers for HVAC
- Refrigerant-based economizers that use the refrigerant cycle to cool air.
- Dew-point economizers cool the air’s dew point to prevent excess humidity from entering a building.
HVAC Economizer Requirements
ASHRAE Standard 90.1-2022 prescriptive requirements for HVAC economizers in comfort cooling applications include the following:
- Airside or waterside economizers are required for “individual fan-cooling units” greater than 54,000 Btu/hr (4.5 tons, 15.8 kW) for all climate zones except 1A and 1B.
- An airside economizer must be capable of providing up to 100 percent of the design supply airflow as outdoor air for cooling.
There are several exceptions in this standard. The Tri-Tech Energy team is up-to-date on the latest requirements set by relevant regulatory bodies.
We understand the needs of our clients. That is why Tri-Tech technicians are available 24 hours a day, 7 days a week for commercial HVAC services that include preventive maintenance. Is the economizer in your HVAC malfunctioning? Contact Tri-Tech today for assistance. You can also visit our website for more information: https://www.tritechenergy.com/